Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM01613
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 8: THE SOILS REPORT USED IN THE DESIGN WAS NOT PROVIDED FOR REVIEW. |
| 07/14/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | need pcrwrd 3rd fl capcityreview & approval - Michael Harrington - 740-6305 |
| 07/27/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/28/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The structural detail (50/S1.5) states that the platform is for a maximum load of 250 pounds but the specified water heater along with the expansion tank results in a load of 401 pounds. Verify that the structural design is adequate for the new load. [Original comment: Provide a design for the mounting shelf for the water heater (WH-2) along with structural calculations to show that the water heater is safely supported. Reference: Section 301.2 IPC 2006.] 2. Comment not resolved. The specified 12"w x 8" h scuppers are adequate for each roof area covered by key note 7.4 and detail 5/A2 but the scupper/collector box assemblies covered by key note 7.9 and detail 6/A2 do not have sufficient dimensions for evaluation. Provide the scupper width, the downspout dimensions, and the size of the overflow cutout. In addition, provide calculations to show that the overflow cutout on the collector box is capable of handling the same flow as the required scupper. [Original comment: Provide roof drainage calculations for each scupper installation and provide additional calculations to show that the overflow cutout on the collector box is capable of handling the same flow as the required scupper. Reference: Sections 1101.7, 1106.1, 1106.2, 1106.4, 1106.5, 1107.1, and1107.3, IPC 2006.] |
| 08/01/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/04/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/04/2011 | SUE REEVES | REJECT SHELF | Completed |