Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01594
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/25/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/25/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The minimum font size for the drawings is 3/32". 2. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. 3. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 4. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson |
| 05/25/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 05/25/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/25/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. All sheets with lettering smaller than 3/32" (upper and lower case) is to be changed to that minimum and resubmitted. 2. Provide a letter from the primary architect or engineer stating new HVAC units load effect on existing roof framing plan. 3. Provide large scale toilet plan showing all accessibility requirements including dimensions, accessoies and fixtures. 4. Provide all accessible dimensions, accessories and fixtures on toilet elevations. 5. Provide a typical interior partition detail showing bracing to structure above. 6. Show existing wall and attachment of the water heater brackets. 7. Provide an accessible drinking fountain. END OF REVIEW |
| 05/25/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 05/25/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide note #7 on sheet P1.0 2. Provide a cleanout for the mop sink. Reference: section 707.4, UPC 2006. 3. Clarify detail 3/P2.0; is it required and if so, where. |
| 05/25/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/25/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/02/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/02/2011 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |