Permit Number: T11CM01594
Parcel: 11307145A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01594
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
05/25/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The minimum font size for the drawings is 3/32".
2. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
3. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
4. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson
05/25/2011 RONALD BROWN ADA REVIEW Passed
05/25/2011 ROBERT SHERRY WATER REVIEW Approved
05/25/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. All sheets with lettering smaller than 3/32" (upper and lower case) is to be changed to that minimum and resubmitted.
2. Provide a letter from the primary architect or engineer stating new HVAC units load effect on existing roof framing plan.
3. Provide large scale toilet plan showing all accessibility requirements including dimensions, accessoies and fixtures.
4. Provide all accessible dimensions, accessories and fixtures on toilet elevations.
5. Provide a typical interior partition detail showing bracing to structure above.
6. Show existing wall and attachment of the water heater brackets.
7. Provide an accessible drinking fountain.
END OF REVIEW
05/25/2011 LOREN MAKUS ENGINEERING REVIEW Approved
05/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide note #7 on sheet P1.0
2. Provide a cleanout for the mop sink. Reference: section 707.4, UPC 2006.
3. Clarify detail 3/P2.0; is it required and if so, where.
05/25/2011 DAVE MANN FIRE REVIEW Approved
05/25/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/02/2011 GERRY KOZIOL WWM REVIEW Approved
06/02/2011 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review