Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM01579
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 1; SHEET A2.1.2 (FLOOR PLAN LEGEND); SHEET A3.1.2 (SECTION 7): THE SECTION INDICATES THE NEW WALL STUDS TO BE 20 GAUGE, 6" METAL STUDS AT 24" O.C., WHILE THE FLOOR PLAN LEGEND INDICATES 3 5/8", 25 GAUGE METAL STUDS AT 24" O.C. CLARIFY AND COORDINATE THE METAL STUD SIZES. 2. GENERAL: PROVIDE WRITTEN RESPONSE TO THE REVIEW COMMENT. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/13/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |