Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/15/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01554
1010 N Palo Verde
17.25 KW Photovoltaic System
5 Arrays-5 Inverters-75 modules

1. Array #2 on Sheet PV1.0 shows 14 modules, and then 12 modules on Sheet PV2.0.
2. The DC calculations on array #2 show Max voltage at 516.6 v, the module voc= 36.9v x 12 = 442.8v, times 1.14=504.7v. The max input on the Inverter spec sheet is 500v ?
3. Sheet PV 2.1, the new 125 amp panel with two 90 amp circuit breakers, 2005 NEC 690.64.B.2--- the sum of the amp ratings of circuit breakers supplying power to the panel not
to exceed the rating of the panel.

Ray Majuta
Elect Pln Ck
PDSD, C of Tuc,
6/20/11