Permit Number: T11CM01526
Parcel: 205630510

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM01526
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2011 SEPTIC APPROVAL WWM REVIEW Denied NEED TO PROVIDE RECORDS OF EXSISTING SEPTIC
06/20/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FOUNDATION PLANS:

1. The PAHD series has been discontinued. Revise the Braced Wall Panel notation at detail 1/A3 with a device and an installation method that provides the required 1800 LBS uplift capacity, R602.10.6.

SECTIONS - DETAILS:

1. Clarify overtype Truss Notes sheet A3, R106.1.1.
2. Remove Unvented Attic-Roof Design notation from sheet A4. This method must include the sealed detail on the plans. The Alternate Method shown on sheet A4 is in compliance with R806.4.
3. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.
4. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.
5. Provide roof scupper openings with a 4" minimum width, IPC 1107.3.

PLUMBING PLANS:

1. Clarify the Gas Demand schedule showing one new furnace for a total of 80,000 rather than 160,000 BTU.
2. Provide gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Extend the 1-1/2" pipe to the branch tee in the utility closet. Show a 1" line to the furnance.

MECHANICAL PLANS:

1. Provide a finished plan without taped-on inserts.
2. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1. Clarify Duct Work notation.

ELECTRICAL PLANS:

1. Designate the circuit number at the location of each appliance, E3603.5. Clarify circuit # 10 & 19.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B, N1101.2. Clarify notation on sheet #A5.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/08/2011 CPIERCE1 OUT TO CUSTOMER Completed