Permit Number: T11CM01520
Parcel: 125170230

Address:
15 N ALVERNON WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01520
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved /
07/20/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/20/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/20/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide listing, capacity, and operating information for the proposed new storage-type water heater being provided by others.
2. Recalculate the size of the gas piping using the developed lengths shown on the drawing.
3. Verify that the rice cookers can be easily moved to provide access to the new floor cleanout, Reference: Sections 706.8 and 706.9, IPC 2006.
07/29/2011 CPIERCE1 WWM REVIEW Needs Review