Permit Number: T11CM01509
Parcel: 136244500

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01509
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/19/2011 ROBERT SHERRY WATER REVIEW Needs Review
05/19/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
05/19/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Doors must swing in direction of travel. IFC Chapter 10.

Rear door needs panic hardware. IFC Chapter 10.

Restaurant is Group A2. IFC Chapter 2

Occupant load of floorplan layout indicates over 100 which would require fire sprinklers. This does not match the occupant load stated in the code review. IFC Chapter 9.
05/19/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
05/19/2011 CAGUILA1 WWM REVIEW Needs Review