Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01509
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/19/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/19/2011 | ROBERT SHERRY | WATER | REVIEW | Needs Review | |
05/19/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
05/19/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Doors must swing in direction of travel. IFC Chapter 10. Rear door needs panic hardware. IFC Chapter 10. Restaurant is Group A2. IFC Chapter 2 Occupant load of floorplan layout indicates over 100 which would require fire sprinklers. This does not match the occupant load stated in the code review. IFC Chapter 9. |
05/19/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
05/19/2011 | CAGUILA1 | WWM | REVIEW | Needs Review |