Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM01486
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01486
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2011 DAVE MANN FIRE REVIEW Approved
06/01/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A0.2
1. The City of Tucson minimum lettering size is 3/32" upper and lower. Please revise all sheets that have lettering smaller than 3/32" and resubmit.
2. Code copied details are not acceptable as element design references. All accessible code requirements are to be included in all actual design large scale floor plans and elevations.
SHEET A4.3
3. Some of the spans for the roll up grilles are 20'. Please clarify the structural steel column support and the structural stability of the roll up grill to span these distances.
SHEET A6.1
4. Details 1, 4 and 5: Ditto comment number 2 above.
5. Details 1 and 6: Clearances at the water dispensers are to comply with ICC/ANSI 117.1, 2003 Edition, Section 602.2.
6. Detail 7: Show all code required accessible dimensions, accessories and fixtures on Details 4 and 5 interior elevations.
7. Please do not forget the vertical grab bar as required by ICC/ANSI 117.1 2003 Edition, Section 604.5.1.
SHEET A6.2
8. Detail 2: redesign the Overall Fitting Room plan to match the large scale accessible plan. Please do the same for all floor plans on Sheets A2.1, A2.3 and A2.3.
9. Detail 6: Please insure all plans and elevations match the large scale accessible plan shown in Detail 2.
END OF REVIEW
06/08/2011 ROBERT SHERRY WATER REVIEW Approved
06/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Specify the maximum temperature of the hot water supply to the public lavatories per Section 504.3, IECC 2006.
2. Provide an upper terminal cleanout for the sink JS-1, or increase the size of the wall cleanout at the floor drain FD-1 to accommodate the 4" building drain. Reference: Sections 707.4 and 707.11, UPC 2006.
06/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
2. Condensate drains may not terminate onto a roof (Coded Note #7, sheet M1.0). Condensate drains may terminate over a roof drain if the roof drain terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. For other options, see Section 307.2.1, IMC 2006, as amended by the City of Tucson.
3. Clarify the design of the restroom and janitorial room exhaust system as shown on sheet M1.0. In addition, provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
06/10/2011 GERRY KOZIOL WWM REVIEW Approved
06/14/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01486
5870 E Broadway #230
TI 18,495 sq ft

Electrical plans denied for following:

1.Sheet E0.3, one line diagram Note 2 (Electrical contractor to verify AIC with Utility), we require the fault current levels be included on the plans for review. As per submittal requirements provide a fault current analysis beginning at the 600 amp main disconnect on through for each panel.
2. Provide 2006 IECC Lighting Budget Calculations as required per Commercial Submittal Requirements, Com Ck ok.


Ray T Majuta,
Elect Pln Review
PDSD,City of Tucson,
6/14/2011
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/27/2011 SUE REEVES OUT TO CUSTOMER Completed
06/27/2011 SUE REEVES REJECT SHELF Completed