Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2011 GERRY KOZIOL WWM REVIEW Approved
05/20/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-21-11
Activity: T11CM01469
Address: 1322 E Spring
Applicant: Levi Conrad

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide north arrow on sheet A-2.0

STRUCTURAL / FRAMING PLAN:
1. Specify grade of lumber to be used in roof framing, R802.1.
2. Justify roof design
o 2x6 @ 24"o.c. is 139% deficient for the proposed span
o Minimum R-30 required in ceiling cavity

SECTIONS - DETAILS:
3. Ceiling gypsum board must be either 5/8" or ½" sag resistant when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.
4. Specify horizontal orientation for 3/8" cdx sheathing, Table R602.3(3)b.
5. Specify uplift resistance for roof framing at both ends of rafters, R802.11.1.

PLUMBING PLAN:
6. Provide the maximum developed length of water line from the meter the furthest appliance served, and the diameter of the water service line, P2903.7.
7. Provide a water fixture unit schedule for the entire property (including existing) P2903.6.
8. Specify water conservation requirements: Water closets = 1.6 gallons per flush, Sinks = 2.2 gpm, Showerheads = 2.5 gpm, P2903.2.
9. Shower and tub/shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
10. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5.

ELECTRICAL PLAN:
11. Include washer and dryer receptacles on electrical design.
12. Bedroom outlets shall be protected with combination-type arc-fault breakers (receptacles, lights, and smoke detectors), E3802.12.
13. Show locations of smoke detectors (every sleeping room and hallways leading to). All smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke detectors, R313.

INTERNATIONAL ENERGY CONSERVATION CODE:
14. Specify the "R" value of the insulation, as well as the "U" factor and the solar heat gain coefficient of the windows and doors. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2011 CPIERCE1 OUT TO CUSTOMER Completed