Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01459
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/13/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide sealed mechanical drawings. 2. Revise the ventilation calculations account for the telephone call center occupancy type (60 people/1000 SF and 6 CFM per occupant). 3. Include AC-1 in the ventilation calculations. |
| 05/13/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/13/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/13/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/13/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 05/13/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide sealed plumbing drawings. 2. Clarify the status of the water heater platform - new or existing ? |
| 05/13/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 05/13/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/13/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 05/18/2011 | CPIERCE1 | FIRE | REVIEW | Needs Review |