Permit Number: T11CM01447
Parcel: 12111019A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01447
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/12/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/12/2011 ERIC NEWCOMB ADA REVIEW Passed
05/12/2011 ROBERT SHERRY WATER REVIEW Approved
05/12/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/18/2011 PAUL MACHADO ENGINEERING REVIEW Approved
05/18/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
05/18/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/18/2011 DAVE MANN FIRE REVIEW Approved
05/19/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T11CM01447
4995 E Speedway
Goodwill TI

Electrical Plans denied for the following:

1. Sump on E-1 shown on circuit K-4, should be K-14.
2. Circuits K 6 and 8 not shown on plan, only in s panel schedule.
3. All meters are required to have and address or suite # for identification, these should also identify the panels.Please ID each meter, main disconnect,and panel the same. Check with addressing to corolate.
4. General note 2 on the one line diagram notes the following:'' Inspect all existing conductors, terminations and
service equipment for signs of deterioation,code issues damages or overloading. Photograph and submit written report to Engineer and Architect of record prior to commencement of work". This is work that is required to be taken care of prior to submiting for a permit.
The wotk entailed in this plan notes replacement of the 800 amp CT enclosure, meters, reusing main disconnects with switches suitable if switches have fuses that protect down stream at levels of 10,000 amp fault current or below.
All of these issues are to be reviewed on site prior to obtaining a permit.
Provide all information on the one line diagram including the service entrance conductors, the size of the gutters on the side of the CT enclosure, the conductors going to the gutters , the existing grounding system etc.
In using the word optional to describe certain installations charges for fees are made to both on the permit fees,please consider this when including aoptional installation.

Ray T Majuta,
Elect Plan Ck,
PDSD, City of Tucson ,
5/19/11
Ray.majuta@tucsonaz.gov
05/26/2011 GERRY KOZIOL WWM REVIEW Approved