Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01442
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2011 | DAVE MANN | FIRE | REVIEW | Denied | Delayed egress limited to 15 seconds per C.O.T. amendments to 2006 IFC, section 1008.1.8.6 (Sheet A912) Unable to verify pump room requirements met (floor drain, lighting, etc) Unable to locate sheet matching (fire protection) hazard locations to key on sheet MP001. Be advised a separate, deferred submittal will be required for fire alarms. |
| 05/17/2011 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 05/20/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM01442 225 N Commerce Park Loop QIP Tucson Office Electrical plans denied for the following: 1. Provide as required per C of T Submittal Requirements 2006 IECC light budget calculations. 2. Provide per C of T Submittal Requirements, 2006 Tucson/Pima County Outdoor Light Calculations. 3. Provide per C of T Submittal Requirements, a Fault Current Analysis beginning at service on through to the panels and equipment downstream and show how the equipment downstream is to be protected from higher than approved levels. 4. Provide a ground system conductor size and show on plan. 5. Provide a ground size conductor for all transformers and show by each transformer. 6. Note on one line diagram that a performance test is required on service per NEC 2005, 230 95.C. 7. Note on service one line that Fire Pump installation to comply with NEC 2005 695 and NFPA 2005. 8. Describe the route the feeder for the Fire Pump will take from the service to the FP, show how it will comply with NEC 2005 230.82.5, and 695.6.A. 9. On service diagram explain what the Disintegrator System is and provide a cut sheet for it. 10. Provide a panel schedule and discription for M3N B01 and M3E B01. 11. Provide a cut sheet for the Busways to be used. 12. M3E BO1 shows a 600 amp CB however has a 400 amp CB at panel. 13.P3E B01 does not have a panel schedule. 14. L3E C01 has a 100MCB however has a 20 amp CB at Pnl L3N C01 feeding the 45kva transformer. 15.P3L B01 panel schedule not provided. 16. The 4 pole disconnects at Busways compared to 3 pole for neutral disconnect ? 17. We are und the 2005 NEC which limits panels to 42 circuits per 408.42. 18. Panel RIE 201 to have the loads rebalanced, phase A is too high. 19. Provide a spec sheet on Fire Pump and the Controller. Please address each individually and indicate how each was resolved. Ray T Majuta, Elect Pln CK,PDSD, City of Tucson, 5/22/11 Ray.Majuta@tucsonaz.gov |
| 05/23/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T003; VOLUME 2: THE SHEET INDEX IS LISTED AS TOOO, WHILE THE ACTUAL SHEET NUMBER INDICATES T003. CLARIFY. 2. SHEET T003; VOLUME 2: SHEETS LS101A THROUGH LS111B ARE NOT LISTED IN THE INDEX. VERIFY. 3. SHEET T003; VOLUME 2: SHEETS A140 AND A141 ARE LISTED OUT OF SEQUENCE IN THE INDEX. VERIFY. 4. SHEET LS101A; CODE SUMMARY: UNDER "PASSIVE FIRE RESISTANCE REQUIREMENTS", CORRIDORS REFERENCE TABLE 1016.1. REVISE. 5. SHEETS LS101A THROUGH LS111B: THE DESIGN PROFESSIONAL MUST SIGN AND DATE HIS SEAL. 6. SHEET LS101A; PLUMBING FIXTURE TABLE: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE TABLE TO MEET THIS REQUIREMENT. 7. SHEET LS104A: DARKEN THE LINES AT THE PENTHOUSE FLOOR PLAN AND ENLARGED FLOOR PLAN TO ENSURE THEY CAN BE SCANNED. 8. SHEET A002; WALLS A1/A1x: THE IBC SECTION 1607.13 REQUIRES INTERIOR WALLS AND PARTITIONS TO HAVE ADEQUATE STRENGTH TO RESIST A 5 PSF HORIZONTAL LOAD. PROVIDE DETAILS FOR BRACING THE TOP OF THE WALL, INCLUDING BRACING SIZES AND SPACING, CONNECTION OF THE BRACING TO THE STRUCTURE ABOVE, AND CONNECTION OF THE BRACING TO THE TOP OF THE WALL. THE NOTE TO "BRACE TO STRUCTURE ABOVE" IS NOT ADEQUATE. 9. SHEET A003; WALLS A11/A11A: REPLACE THE NOTES "METAL STUD FRAMING AS REQUIRED" AND "LATERAL SUPPORT TO STRUCTURE ABOVE AS REQUIRED" WITH FRAMING SIZES, SPACING, AND ALL CONNECTIONS. 10. SHEET A004; SHOWER STALL PLAN C14: PER THE IBC SECTION 1109.2, BATHING FACILITIES SHALL BE ACCESSIBLE. PROVIDE GRAB BARS IN THE ACCESSIBLE SHOWERS PER ANSI SECTION 608.3. 11. SHEET A004; SHOWER STALL PLAN C14: PROVIDE A DESCRIPTION OF "P" AND "Q" ON THIS SHEET. 12. SHEET A004; ELEVATION E11: PROVIDE A VERTICAL GRAB BAR PER ANSI FIGURE 604.5.1. 13. SHEET A101; FLOOR PLAN: BUILDING SECTIONS REFERENCE SHEETS A401 AND A405. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 14. SHEET A101; FLOOR PLAN: BUILDING ELEVATIONS REFERENCE SHEETS A151, A300, AND A310. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 15. SHEET A101A; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL TYPE REFERENCES TO MEET THIS REQUIREMENT. 16. SHEET A101A; FLOOR PLAN: BUILDING SECTIONS AND DETAILS REFERENCE SHEETS A151, A152, A401, A410, A411, A412, A511, A512, A601, AND A611. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 17. SHEET A101A; FLOOR PLAN: BUILDING AND WALL ELEVATIONS REFERENCE SHEETS A300 AND A310. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 18. SHEET A101B; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL TYPE REFERENCES TO MEET THIS REQUIREMENT. 19. SHEET A101B; FLOOR PLAN: BUILDING SECTIONS AND DETAILS REFERENCE SHEETS A405, A412, A413, A414, A415, A503, A511, A512, AND A603. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 20. SHEET A101B; FLOOR PLAN: BUILDING AND WALL ELEVATIONS REFERENCE SHEETS A300, A310, AND A312. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 21. SHEET A102A; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL TYPE REFERENCES TO MEET THIS REQUIREMENT. 22. SHEET A102A; FLOOR PLAN: BUILDING SECTIONS AND DETAILS REFERENCE SHEETS A151, A401, A511, A512, A601, AND A611. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 23. SHEET A102A; FLOOR PLAN: BUILDING AND WALL ELEVATIONS REFERENCE SHEETS A300 AND A310. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 24. SHEET A102B; ROOF PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL TYPE REFERENCES TO MEET THIS REQUIREMENT. 25. SHEET A102B; ROOF PLAN: BUILDING SECTIONS REFERENCE SHEETS A405, A414, AND A503. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 26. SHEET A102B; ROOF PLAN: BUILDING ELEVATIONS REFERENCE SHEETS A310 AND A312. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 27. SHEET A103A; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL TYPE REFERENCES TO MEET THIS REQUIREMENT. 28. SHEET A103A; FLOOR PLAN: BUILDING SECTIONS AND DETAILS REFERENCE SHEETS A151, A401, A410, A411, A412, A511, A512, A601, AND A611. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 29. SHEET A103A; FLOOR PLAN: BUILDING ELEVATIONS REFERENCE SHEETS A300, A310 AND A311. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 30. SHEET A104A; ROOF PLAN: BUILDING SECTIONS AND DETAILS REFERENCE SHEETS A401, A410, A411, A412, A502, AND A611. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 31. SHEET A104A; ROOF PLAN: BUILDING ELEVATIONS REFERENCE SHEETS A300 AND A310. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 32. SHEET A105; PLAN A14 AND SECTION A6: THE SECTION REFERENCES SHEET A417. THIS SHEET IS NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 33. SHEET A105; PLAN H14: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL TYPE REFERENCES TO MEET THIS REQUIREMENT. 34. SHEET A105; PLAN H14: THE WALL SECTIONS REFERENCE SHEETS A417 AND A420. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 35. SHEET A105; PLAN H14: BUILDING ELEVATIONS REFERENCE SHEET A314. THIS SHEET IS NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 36. SHEET A106; PLAN: WALL SECTIONS AND DETAILS REFERENCE SHEETS A420 AND A421. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 37. SHEET A106; PLAN: WALL ELEVATIONS REFERENCE SHEETS A315, A316, A317, AND A420. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 38. SHEET A107; PLANS: SECTIONS REFERENCE SHEET A420. THIS SHEET IS NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 39. SHEET A107; PLANS: BUILDING AND WALL ELEVATIONS REFERENCE SHEETS A314, A316, AND A317. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 40. SHEET A111; PLAN: SECTIONS AND DETAILS REFERENCE SHEETS A405, A416, A503, AND A603. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 41. SHEET A111; PLAN: BUILDING AND WALL ELEVATIONS REFERENCE SHEET A300. THIS SHEET IS NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 42. SHEET A112; PLAN: SECTIONS AND DETAILS REFERENCE SHEETS A405, A416, A503, AND A603. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 43. SHEET A112; PLAN: BUILDING AND WALL ELEVATIONS REFERENCE SHEET A300. THIS SHEET IS NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 44. SHEET A113; PLAN: SECTIONS REFERENCE SHEETS A401, A405, A416, A503, AND A603. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 45. SHEET A113; PLAN: BUILDING AND WALL ELEVATIONS REFERENCE SHEETS A300 AND A310. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 46. SHEET A140: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL TYPE REFERENCES TO MEET THIS REQUIREMENT. 47. SHEET A140: SECTIONS AND DETAILS ON VARIOUS PLANS REFERENCE SHEETS A401, A411, A413, A511, A602, AND A611. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 48. SHEET A141: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL TYPE REFERENCES TO MEET THIS REQUIREMENT. 49. SHEET A141; PLAN K14: SECTIONS REFERENCE SHEETS A401 AND A611. THESE SHEETS ARE NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 50. SHEET A201A; PLAN: A WALL SECTION REFERENCES SHEET A152. THIS SHEET IS NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 51. SHEET A201A; PLAN: ROOMS 107, 109, 113, 139, AND 141 HAVE CEILING HEIGHT DESIGNATIONS COVERING ROOM DESIGNATIONS. CLEAR UP. 52. SHEET A202A; PLAN: CLEAR UP THE ROOM REFERENCE NUMBER AND NAME IN ROOM C208. 53. SHEET A203A; PLAN: REMOVE OR PROVIDE THE ROOM REFERENCE NUMBERS FROM THE ELEVATORS ON GRID G. 54. SHEET A804; ELEVATION D10: A SECTION REFERENCES SHEET A411. THIS SHEET IS NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 55. SHEET A804; ELEVATION F8: A SECTION REFERENCES SHEET A151. THIS SHEET IS NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 56. SHEET A804; ELEVATION D10: A SECTION REFERENCES SHEET A602. THIS SHEET IS NOT INCLUDED IN THIS REVIEW SET, OR INDICATED IN THE INDEX. PROVIDE. 57. SHEET A806; ELEVATION A5: PROVIDE A VERTICAL GRAB BAR PER ANSI FIGURE 604.5.1. 58. GENERAL: CHECK THE LINE WEIGHTS ON ALL DRAWINGS TO ENSURE THEY CAN BE SCANNED. 59. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/26/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 06/06/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | Provide that last approved development plan or site plan. |
| 06/08/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/08/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/09/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. 2. Revise sheet M301D so that the background is visible. Reference: Section 106.3.1, IMC 2006. 3. Coordinate the fire damper and smoke damper locations with the fire-rated walls shown on sheets LS101A, LS101C: see M301A (VAV 1-08, room 127 smoke, room 125 fire; VAV 1-10, room 131 fire; VAV 1-11, room C104 fire; VAV O-11 and transfer duct, room 112A, fire; VAV O-06, room 132 fire; room 133B transfer duct, fire) and M301B (room A104B transfer duct, smoke). Reference: Sections 106.3.1 and 607.1, IMC 2006 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/20/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 06/20/2011 | SUE REEVES | REJECT SHELF | Completed |