Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) RACKING DESIGN ON PLAN SHEETS DOES NOT MATCH ENGINEERING CALCULATIONS, HAS CONFLICTS IN LISTED DIMENSIONS, AND IS LACKING CONNECTION DETAILS.

1a) DIMENSIONS SHOWN ON PLAN SHEETS BETWEEN DIFFERENT COMPONENTS MUST BE LESS THAN OR EQUAL TO THE DIMENSIONS IN THE CALCULATIONS.

1b) DIMENSIONS SHOWN ON PLAN SHEET FOR CENTER TO CENTER DISTANCES MUST NOT CONFLICT.

1c) PLEASE PROVIDE COMPLETE DETAILS FOR ALL MECHANICAL CONNECTIONS (DO NOT MAKE REFERENCES SUCH AS "INSTALL PER MANUFACTURER".)

1d) ANY MECHANICAL CONNECTION DETAILS THAT ARE DERIVED FROM A PARTICULAR MANUFACTURER MUST BE ACCOMPANIED BY CUT-SHEETS FROM THAT MANUFACTURER.

FOR QUESTIONS OR COMMENTS CONCERNING THIS PLAN REVIEW PLEASE E-MAIL THIS REVIEWER AT:
LeeRay.Hanly@tucsonaz.gov

1a) CALCULATIONS CONSIDER A RACKING SYSTEM OF UNISTRUT MAX 2'9" O.C. (HOLDING PANELS); MOUNTED PERPENDICULARY TO 5'6" O.C.TRIANGLE BRACING; WHICH IN TURN IS MOUNTED TO ANOTHER SET OF PARALLEL UNISTRUT WITH