Permit Number: T11CM01431
Parcel: 13317064B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01431
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2011 STEVE SHIELDS ZONING REVIEW Approved
05/11/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/11/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/11/2011 ROBERT SHERRY WATER REVIEW Approved
05/11/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/11/2011 PAUL MACHADO ENGINEERING REVIEW Approved
05/11/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The plumbing specification shows ABS or PVC waste and vent piping being installed within a return air plenum. Revise the materials to comply with Section 602.2.1, IMC 2006.
05/11/2011 DAVE MANN FIRE REVIEW Approved
05/11/2011 ERIC NEWCOMB ADA REVIEW Passed
05/11/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/17/2011 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/17/2011 DELMA ROBEY OUT TO CUSTOMER Completed