Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01399
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/10/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/11/2011 | GERRY KOZIOL | WWM | REVIEW | Passed | |
05/23/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/25/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/25/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/26/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the specified machinery room ventilation system (EF-1 and EF-2) complies with Section 1105, IMC 2006 for normal and emergency ventilation quantities and for the discharge location of the ventilation air. 2. Show that the gas train (i.e. regulators, manual valves, and vents for the boilers) comply with the requirements of Section 410, IFGC 2006. |
06/06/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/21/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |