Permit Number: T11CM01399
Parcel: 117200270

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01399
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2011 MARTIN BROWN FIRE REVIEW Approved
05/11/2011 GERRY KOZIOL WWM REVIEW Passed
05/23/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/25/2011 ROBERT SHERRY WATER REVIEW Approved
05/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/26/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the specified machinery room ventilation system (EF-1 and EF-2) complies with Section 1105, IMC 2006 for normal and emergency ventilation quantities and for the discharge location of the ventilation air.
2. Show that the gas train (i.e. regulators, manual valves, and vents for the boilers) comply with the requirements of Section 410, IFGC 2006.
06/06/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2011 DELMA ROBEY OUT TO CUSTOMER Completed