Permit Number: T11CM01365
Parcel: 13220003A

Address:
3401 E GAS RD

Review Status: Completed

Review Details: SITE

Permit Number - T11CM01365
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2011 MARTIN BROWN FIRE REVIEW Approved
05/11/2011 ERIC NEWCOMB H/C SITE REVIEW Needs Review
05/18/2011 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T11CM01365
3401 E. Gas Rd.
Site Plan

TRANSMITTAL DATE: 05/19/11

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Provide two copies of the last approved site plan. Cloud the area of construction on these plans and reference to the sheet 3 of 4. Required for the amount of parking provided, FAR calculations, expansion calculations, etc.

2. This is a minor change and I will review over the counter. Please call and make an appointment.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T11CM01365.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
05/23/2011 ANDREW CONNOR LANDSCAPE REVIEW Passed
05/24/2011 ANDREW CONNOR NPPO REVIEW Passed
06/06/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the gas meter
c. the location of the building connection to the public sewer
d. the location, invert, and rim elevation of all manholes and cleanouts
e. the first floor elevation for the building
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/08/2011 CPIERCE1 OUT TO CUSTOMER Completed
06/08/2011 SUE REEVES REJECT SHELF Completed