Permit Number: T11CM01351
Parcel: 110120960

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T11CM01351
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2011 DAVE MANN FIRE REVIEW Approved
05/10/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied STRUCTURAL PAGES:

1) PLEASE PROVIDE GEO-TECH REPORT

2) PP S-501 DETAIL 8, NO SPECIFICATIONS MADE FOR WELD ATTACHMENT (NOTES SAY "AS REQUIRED")

3) NOTE ONLY--NOT CORRECTION; DEFERRED SUBMITTAL SHALL BE ACCEPTED FOR PC CONCRETE AS CALLED FOR IN GENERAL NOTE 8, PP S-001. ALL SHOP DRAWINGS FROM PC FABRICATOR TO BE SUBMITTED TO C.O.T. AFTER ENGINEER OF RECORD HAS REVIEWED AND ACCEPTED THEM.

ARCHITECTURAL PAGES:

1) PER 2006 IBC YOU MUST PROVIDE 13 ACCESSIBLE PARKING SPACES FOR THIS GARAGE. PLEASE NOTE ON PLANS WHICH SPACES ARE ACCESSIBLE. AS AN ALTERNATIVE YOU MAY PROVIDE A CAMPUS SITE PLAN SHOWING HOW ACCESSIBLE PARKING REQUIREMENTS ARE BEING MET.

2) PP A-005 GENERAL BUILDING NOTE FOR ACTUAL HEIGHT INDICATES 3'9" PLEASE CORRECT.

3) PP A-011 FOURTH FLOOR PLAN HAS GRIDMARK DESIGNATIONS OVERWRITTEN MAKING THEM ILLEGIBLE.

4) STRIPING PLANS HAVE KEYNOTE INDICATORS WITHOUT ANY ASSOCIATED KEYNOTES.

5) PP A-202 PLEASE SPECIFY FASTNER NOTED IN DETAIL FOR HORIZONTAL 16 GA GALVANIZED STEEL.

6) PP A-515 DETAILS B4 & B6 REFERENCE STRUCTURAL DRAWINGS FOR PANEL CONNECTIONS TO COLUMNS, I'M ASSUMING YOU MEAN TO REFERENCE THE PC SHOP DRAWINGS.
05/16/2011 GERRY KOZIOL WWM REVIEW Denied NEED SITE PLAN LOCATING PARKING STRUCTURE TO IDENTIFY ANY CONFLICTS WITH ON-SITE PRIVATE SEWER.
05/18/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/18/2011 ROBERT SHERRY WATER REVIEW Approved
05/19/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE IECC COMPLIANCE CERTIFICATE FOR LIGHTING

2) PLEASE PROVIDE INFORMATION, INCLUDING LUMINAIRE CUT SHEETS FOR VERIFICATION OF COMPLIANCE WITH THE CITY OF TUCSON OUTDOOR LIGHTING CODE.

3) PP E301 DETAIL 7 NOTES INDICATES CONCRETE IN DUCT BANK BUT DETAIL DOES NOT SHOW IT. PLEASE REVISE.

4) PP E-303 DETAIL 2 CUT A-- NOTES INDICATE EXISTING POLE TO BE REUSED. PLEASE PROVIDE INFORMATION ON WHERE POLE IS COMING FROM, WITH SPECIFICATIONS ON MATERIAL TYPE. IF POLE IS TO BE PER LIGHT FIXTURE SCHEDULE PP E-401 PLEASE PROVIDE CUT SHEET AND REVISE NOTE ON DETAIL.
06/01/2011 TERRY STEVENS ZONING REVIEW Denied 06/01/2011

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
06/02/2011 ELIZABETH LEIBOLD ENGINEERING REVIEW Denied Provide on cover sheets a location plan for the parking structure indictating location on TMC campus.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2011 CPIERCE1 OUT TO CUSTOMER Completed
06/28/2011 SUE REEVES REJECT SHELF Completed