Permit Number: T11CM01317
Parcel: 132082240

Address:
1991 E AJO WY

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01317
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2011 DAVID RIVERA ZONING REVIEW Approved
05/02/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide a complete mechanical design per the 2006 International Mechanical Code, with local amendments.
3. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
05/02/2011 ERIC NEWCOMB ADA REVIEW Passed
05/02/2011 ROBERT SHERRY WATER REVIEW Approved
05/02/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. CITY OF TUCSON REQUIRES PLANS TO INCLUDE A CODE ANALYSIS ON THE DRAWINGS, INCLUDING OCCUPANCY TYPE, OCCUPANCY LOAD, PERTINENT BUILDING CODES, ETC.
2. PROVIDE A SITE PLAN (MAY USE EXISTING PLAN FROM PREVIOUS PROJECT) IN THE SET OF DRAWINGS.
3. MAKE SURE ALL TEXT IS A MINIMUM OF 3/32" HEIGHT (UPPER AND LOWER CASE) ON ALL SHEETS.
4. LIST ALL PROPERTIES OF CONSTRUCTION MATERIALS, AND DETERMINE SPECIAL INSPECTIONS REQUIRED.
5. DETERMINE IF IMPACT FEE WAS PAID ALONG WITH THE SHELL CONSTRUCTION. IF SO, BRING A LETTER FROM THE BUILDING OWNER INDICATING IMPACT FEE WAS PREVIOUSLY PAID.
6. ON SHEET H3, INDICATE A VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003.
05/02/2011 PAUL MACHADO ENGINEERING REVIEW Approved
05/02/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. The 2006 IPC with Local Amendments may also be used if desired; specify which code has been used.
2. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
3. Provide equipment data for the water heater. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief (if located above the hot water outlets), and valves. Reference: Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2006.
4. Clarify how the water is mounted on the wall. Reference: Section 103.2.3, UPC 2006.
5. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for storage occupancy (e.g. a drinking fountain).
6. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc) Reference: Sections 301.1.1 and 401.1, UPC 2006.
7. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
8. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference: Section 101.5.1, UPC 2006.
05/02/2011 DAVE MANN FIRE REVIEW Approved
05/02/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/03/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied No electrical plans, RTMajuta,5/3/11
06/13/2011 CPIERCE1 WWM REVIEW Needs Review