Permit Number: T11CM01305
Parcel: 11615088L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01305
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2011 GERRY KOZIOL WWM REVIEW Approved
05/03/2011 DAVE MANN FIRE REVIEW Approved
05/13/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide Special Inspection Certifications as outline on sheet S0.1.
SHEET A1.1
2. The following doors do not comply with ICC (ANSI 117.1, 2003 Edition), Section 404.2.3.1, and Figure (a): 104, 106, 110 and 130.
3. Please insure accessibility of the owner furnished check in counter as per ICC (ANSI 1171.), Section 904.
SHEET A3.4
4. Please show all code required accessible dimensions, clearances, accessories and fixtures on the actual designed floor plans and elevations.
a. As per note 10, accessible clearances are not shown on sheet G1.2.
b. Generic code copied details are not acceptable as the final architectural design.
5. Please provide for exposed lavatory water and waste pipe insulation as required by ICC (ANSI 117.1), Section 606.6.
END OF REVIEW
05/18/2011 ROBERT SHERRY WATER REVIEW Approved
05/19/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide backflow protection for the potable water connection to the water softener serving fan coils FC-1 through FC-4. Reference: Sections 608.1, 608.12, and 608.16.6, IPC 2006.
05/19/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the minimum insulation specified for the chilled water piping to comply with the requirements of Section 503.2.8, IECC 2006. ((Note that the chilled water pipe insulation specification, 230700, 2.2, does not include 2" pipe.)
2. Clarify the duct smoke detector note in detail 2/M2.1 that states, "Not required on new HP-4, comm. room". Where does this occur? Reference: Section 106.3.1, IMC 2006.
3. Detail 3/M2.1 calls for insulating the cryogen vent pipe per the specifications. Where are these insulation requirements specified? Reference: Section 106.3.1, IMC 2006.
4. The design of a cryogen vent pipe is critical to the safe operation of an MRI; the design of the cryogen vent pipe constitutes the practice of engineering and requires plans sealed by an Arizona Registrant. Provide sufficient detail to show how a cryogen vent pipe meeting the MRI manufacturer's requirements is to be constructed. Reference: Section 3203.3, IFC 2006 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
5. Identify the exclusion zone at the discharge area for the cryogen vent pipe and specify appropriate warning signs. Reference: Section 3203.5.1, IFC 2006.
05/20/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01305
TI Medical Imaging Center


Need to provide 2006 IECC lighting calculations.

Ray T Majuta
Elect Pln Ck,PDSD,
City of Tucson,
05/24/11

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2011 DELMA ROBEY OUT TO CUSTOMER Completed