Permit Number: T11CM01301
Parcel: 117160030

Address:
119 E TOOLE AV

Review Status: Active

Review Details: SITE

Permit Number - T11CM01301
Review Name: SITE
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2011 Any LANDSCAPE REVIEW Active
05/04/2011 ANY NPPO REVIEW Active
05/04/2011 JASON GREEN ENGINEERING REVIEW Active
05/05/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

1. Stairs and railings were installed without permits. Show complete compliance with IFC Chapter 10.

2. The occupancy has an A2 componant added. Show new occupant load calculations. Occpant load is shown as both 29.4 and 59.4. An A2 occupancy would likely require the extension of the sprinklers from the basement. If this is an F2 a fire separation will be required to the M occupancy next door. Provide new area calculations for the new occupancies. The information on this sheet shows an increase for sprinklers. This is only allowable if the building is fully sprinklered.
05/05/2011 TERRY STEVENS ZONING REVIEW Denied Client has decided to submit through the IID Core Overlay which requires a Development Plan or with a letter from the Zoning Administrator applying through the 10835 process.
05/09/2011 RBROWN1 ADA REVIEW Passed
05/12/2011 RONALD BROWN H/C SITE REVIEW Denied 1. Please provide an accessible route from 7th Av. Reference Zoning comments.
2. Please provide two accessible parking spaces in the parking lot complete with signage and accessible parking aisle.
a. Please provide a large scale detail showing all dimensions, "Van accessible" parking space, slopes, signage, access to accessible route, aisle, and accessible symbols.
3. Provide an accessible route from the new accessible parking spaces to the building accessible route. Reference zoning comments for material of accessible route to building.
4. Please provide a large scale detail of all existing ramps showing all dimensions, height elevations, handrails, slopes and landings.
a. Any ramp with slopes greater than 5% requires handrails.
5. Provide guardrails at the covered porch parallel to Toole Avenue.
END OF REVIEW
10/04/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approved