Permit Number: T11CM01290
Parcel: 120052720

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01290
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2011 MARTIN BROWN FIRE REVIEW Approved
05/12/2011 GERRY KOZIOL WWM REVIEW Approved
05/19/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A4.1
1. Generic code copied details are not acceptable. Please provide all accessible code requirements (dimensions, accessories and fixtures) on to the actual designerd floor plan and elevations.
2. The 2006 IBC is the adopted building code for the City of Tucson. Chapter 11 and ICC (ANSI 117.1, 2003 Edition) is the required accessible code.
a. Please delete all references to ADA.
b. Please delete all ADA dimensions and standards from the elevations and use ICC (ANSI) dimensions and requirements.
3. At detail 12:
a. Please show required clearances at urinals, lavs and water dispensers.
b. Please provide one compliant urnial as per Sections 305 and 605.
SHEET 4.1.1
4. Please indicate 5% of all seating to be accessible as per section 1108.2.8.1.
END OF REVIEW
05/20/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/03/2011 ROBERT SHERRY WATER REVIEW Approved
06/03/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/03/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2011 CPIERCE1 OUT TO CUSTOMER Completed
06/15/2011 SUE REEVES REJECT SHELF Completed