Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM01276
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/09/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units, AC-1 and AC-3. Reference: Section 302.1, IMC 2006. 2. Clarify the note on sheet M3.1, "Exist. 1" plumbing VTR"; condensate drains may not terminate at or over a plumbing vent. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson and Section 311.4, UPC 2006. |
| 08/09/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the existing conditions of the natural gas distribution piping. On sheet P1.1, AC-14 is noted as having a developed length of 400 feet but on sheet P1.2, the branch that serves AC-14 is noted as having a maximum developed length of 350 feet. In addition, on sheet P1.2, the existing 3" branch that heads south from the meter has a load of 1685 CFH with a developed length of 400 feet which is undersized. Reference: Section 402.2, IFGC 2006. |
| 08/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/22/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 08/22/2011 | SUE REEVES | REJECT SHELF | Completed |