Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM01276
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2011 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 06/10/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | 1. The width of the space to the accessible urinal must be 3'0" when depth access is 2'-0" or more. Reference ICC./ANSI 117.1, Section 605.3 and 305. |
| 06/27/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/27/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Installation of duct smoke detectors only in the supply ducts of air-handling units that share a common return air plenum does not comply with the requirements of Section 606.2, IMC 2006. If it is impossible to install the duct smoke detectors in the return ducts of the air-handling units as required by Section 606.2, IMC 2006, provide an approved area smoke detector system located in the return air plenum serving the air handling units. Reference: Section 606.2.2, exception (2), IMC 2006 and NFPA 72-02. |
| 07/07/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/07/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 07/07/2011 | SUE REEVES | REJECT SHELF | Completed |