Permit Number: T11CM01276
Parcel: 10408093B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01276
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2011 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
06/10/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond 1. The width of the space to the accessible urinal must be 3'0" when depth access is 2'-0" or more. Reference ICC./ANSI 117.1, Section 605.3 and 305.
06/27/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/27/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Installation of duct smoke detectors only in the supply ducts of air-handling units that share a common return air plenum does not comply with the requirements of Section 606.2, IMC 2006. If it is impossible to install the duct smoke detectors in the return ducts of the air-handling units as required by Section 606.2, IMC 2006, provide an approved area smoke detector system located in the return air plenum serving the air handling units. Reference: Section 606.2.2, exception (2), IMC 2006 and NFPA 72-02.
07/07/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2011 SUE REEVES OUT TO CUSTOMER Completed
07/07/2011 SUE REEVES REJECT SHELF Completed