Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T11CM01276
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 04/29/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/29/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/04/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/09/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. The minimum font size for all drawings is 3/32" upper and lower case. Please change all sheets that have letting smaller that 3/32" and resubmit. 2. For Sheet G1.02 and detail L1/A203: a. Generic code copied details are not acceptable as the final design detail. b. All accessible dimensions and accessories are to be designed and shown on the actual floor plan layout (L1/A2.03) and elevations (J7 and J13/A7.01). Reference ICC (ANSI 117.1), Section 603, 604, 605, 606 and 305. 3. At detail L1/A2.02: a. Door nos. 160B and 158 are non-compliant, reference ICC (ANSI 117.1), Section 404.2.3.1. 4. Please provide Special Inspection Certifications as outlined on sheets S1.0 and S1.1. 5. Please include structural calculations for the Service Drive Framing Plan and the Patio Extension foundation plan. 6. Please provide the total building occupancy load for issuance of a new Certificate of occupancy. END OF REVIEW |
| 05/13/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/16/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Installation of duct smoke detectors only in the supply ducts of air-handling units that share a common return air plenum does not comply with the requirements of Section 606.2, IMC 2006. If it is impossible to install the duct smoke detectors in the return ducts of the air-handling units as required by Section 606.2, IMC 2006, provide an approved area smoke detector system located in the return air plenum serving the air handling units. Reference: Section 606.2.2, exception (2), IMKC 2006 and NFPA 72-02. 2. Clarify the termination point for the condensate from FC-B and FC-B. Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson. 3. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
| 05/16/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments; the 2006 IBC and 2006 IECC codes are also currently applicable. (See Plumbing General Notes on sheet P2.1) 2. The plumbing general notes on sheet P2.1 contain two roof drainage notes that directly contradict the current roof drain design, please remove the two items. |
| 05/16/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM01276 625 W Auto Mall Remodel / Addition Please provide 2006 IECC Budget Lighting Calculations for relighted areas. Ray T Majuta, Elect Pln Ck PDSD, City of Tucson, 5/18/11 Ray.majuta@tucsonaz.gov |
| 05/19/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 05/26/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |