Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T11CM01200
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Move tire storage to original 20 feet from ALL property lines or fully comply with current IFC Section 2505.
06/20/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; this drawing will be the approved site plan and must provide the information required by Development Standard No. 2-01.0.0. Revise the site drawing to include the following information:
a. the location of the main water lines and fire hydrants
b. the location of the gas meter (if one exists or is planned)
c. the location and size of the public sanitary sewer
d. the location, invert, and rim elevation of all manholes and cleanouts
e. the first floor elevation for the building
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
07/07/2011 DROBEY1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2011 DELMA ROBEY OUT TO CUSTOMER Completed