Permit Number: T11CM01200
Parcel: 13705127A

Address:
4920 S 12TH AV

Review Status: Completed

Review Details: SITE

Permit Number - T11CM01200
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Move tire storage to original 20 feet from property line or fully comply with current IFC Section 2505.
05/12/2011 RBROWN1 ADA REVIEW Passed
05/16/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Menny's Tire Shop - Parking Reconfig.
T11CM01200
Site Plan (1st Review)

TRANSMITTAL DATE: May 16, 2011

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the areas of modification.

2. D.S. 2-02.2.1.A.7 The street perimeter yard setback shown under "LAND USE CODE CHECK" is not correct. Per LUC Section 3.2.6.5.B the required perimeter yard setback is 21' or the height of the structure (H) measured from the back of existing and future curb.

3. D.S. 2-02.2.1.A.9 As you have elected to use Ordinance 10886 for your vehicle parking requirements you must also use the bicycle parking from Per Ordinance 10886. Short-Term and Long-Term bicycle parking is required see comment 4 below. Show the location for the required bicycle parking on the site plan and provide a detail that includes materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports; and the location and type of directional signage.

4. D.S. 2-02.2.A4 The bicycle parking calculation is not correct. Per Ordinance 10886 LUC Section 3.3.8.2B Commercial Use Group, the minimum Short-term requirement is 2, and the minimum Long-Term is 2.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\2011\t11cm01200

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan.
05/17/2011 RONALD BROWN H/C SITE REVIEW Approved
06/02/2011 ANDREW CONNOR LANDSCAPE REVIEW Passed
06/02/2011 ANDREW CONNOR NPPO REVIEW Approved
06/02/2011 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved
06/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. the location of the gas meter (if one exists or is planned)
d. the location and size of the public sanitary sewer
e. the location of the building connection to the public sewer
f. the location, invert, and rim elevation of all manholes and cleanouts
g. the first floor elevation for the building
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2011 CPIERCE1 OUT TO CUSTOMER Completed
06/16/2011 SUE REEVES REJECT SHELF Completed