Permit Number: T11CM01199
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01199
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2011 TERRY STEVENS ZONING REVIEW Approved
04/21/2011 PAUL MACHADO ENGINEERING REVIEW Approved
04/22/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01199
5870 E Broadway 103

Electrical comments: need to describe and size new transformer feeding Pnl L1

R T Majuta
Elect Pln Ck
PDSD, C of Tuc
4/22/11
04/22/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/22/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE CODE ANALYSIS ON DRAWINGS.
2. 2006 IBC, SECTION 1607.13, REQUIRES BRACING AT THE TOP OF NEW PARTITION WALLS TO RESIST LATERAL LOADS. PROVIDE A DETAIL(S) ON THE DRAWINGS INDICATING BRACING SIZE AND SPACING, CONNECTION TO THE TOP OF THE PARTITION WALL, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE.
04/22/2011 ROBERT SHERRY WATER REVIEW Approved
04/22/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/22/2011 MARTIN BROWN FIRE REVIEW Approved
04/22/2011 ERIC NEWCOMB ADA REVIEW Passed
04/22/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/26/2011 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2011 DELMA ROBEY OUT TO CUSTOMER Completed