Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM01151
Parcel: 12510003F

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T11CM01151
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11cm01151 ,Revision #1
Electrical plan denied for following:

1. Provide original plan in order to check revision.
2. Why is another service being added to this structure ? How does this comply with 2005 NEC 230.2 for number of services to a structure ?

Ray Majuta,
Elect Pln Ck,PDSD
City of Tucson
8/9/11
Ray.majuta@tucsonaz.gov