Permit Number: T11CM01151
Parcel: 12510003F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01151
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2011 DROBEY1 FIRE REVIEW Denied
04/25/2011 GERRY KOZIOL WWM REVIEW Denied need to show on drawings all addresses including suite #'s of all areas to be demo'd
need to identify on drawings all wastewater plumbing fixtures to be removed in each suite
need PCRWRD/3rd fl credit evaluation-Karen-740-6344.
05/05/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; KEY NOTES: NOTE 3 INDICATES A SOILS ENGINEER MADE RECOMMENDATIONS ADDRESSING THE EXISTING BASEMENT. IF A REPORT WAS PRODUCED, PROVIDE TO THE CITY OF TUCSON FOR REVIEW.
2. SHEETS A1.0/A1.1; KEY NOTES: NOTE 4 INDICATES THERE IS A SOILS REPORT ADDRESSING THE REMOVAL OF CAISSONS. PROVIDE THAT REPORT TO THE CITY OF TUCSON FOR REVIEW.
3. SHEET A2.0; KEY NOTES: ON KEY NOTE 6, INDICATE THE SPECIFIC 2X WOOD FRAMING MEMBER SIZE.
4. SHEET A2.1; KEY NOTES: ON KEY NOTE 6, INDICATE THE SPECIFIC 2X WOOD FRAMING MEMBER SIZE.
5. SHEET A2.1; DETAILS 04, 06, AND 08 (KEY NOTES 1): INDICATE THE SPECIFIC 2X WOOD FRAMING MEMBER SIZE.
6. SHEET A3.0; ELEVATIONS 03, 04, AND 05: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. SEVERAL OF THE KEY NOTE REFERENCES SHOULD BE REVISED.
7. SHEET A3.2; ELEVATIONS 01 AND 02: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. SEVERAL OF THE KEY NOTE REFERENCES SHOULD BE REVISED.
8. SHEETS S1.1 AND S1.2; DEMOLITION PLAN NOTES: NOTE 3 INDICATES THERE IS A SOILS REPORT ADDRESSING BACKFILL AT THE BASEMENT. PROVIDE THAT REPORT TO THE CITY OF TUCSON FOR REVIEW.
9. SHEETS S1.1 AND S1.2; DEMOLITION PLAN NOTES: NOTE 4 INDICATES A SOILS ENGINEER MADE RECOMMENDATIONS ADDRESSING THE EXISTING BASEMENT. IF A REPORT WAS PRODUCED, PROVIDE TO THE CITY OF TUCSON FOR REVIEW.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/13/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2011 DELMA ROBEY OUT TO CUSTOMER Completed