04/22/2011 GERRY KOZIOL WWM REVIEW Denied need to show on drawings all addresses including suite #'s of all areas to be demo'd
need to identify on drawings all wastewater plumbing fixtures to be removed in each suite
need PCRWRD/3rd fl credit evaluation-Karen-740-6344.
04/28/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01150
5870 E BROADWAY #230
TI SERVICE REMODEL


Electrical plans denied for following:

Provide fault current levels at panels, Electrical Specifications on sheet E2 # 9 indicate RK1 fuses, however
levels at individual panels not known.



Ray T Majuta,
Elect Pln Ck,PDSD,
City of Tucson,
5/2/11