Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2011 MARTIN BROWN FIRE REVIEW Approved
04/20/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
04/20/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/20/2011 ROBERT SHERRY WATER REVIEW Approved
04/20/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. NEW DRINKING FOUNTAIN MUST BE A HIGH/LOW WATER COOLER OR A SINGLE POINT OF USE WATER DISPENSER. REVISE.
04/20/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a vacuum relief for the storage-type water heater located above any fixture outlets. Reference: Section 608.7, UPC 2006
04/20/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/20/2011 ERIC NEWCOMB ADA REVIEW Passed
05/03/2011 CPIERCE1 WWM REVIEW Needs Review
05/03/2011 CPIERCE1 ZONING REVIEW Needs Review
05/03/2011 CPIERCE1 ENGINEERING REVIEW Needs Review