Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM01131
Parcel: 13502134M

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01131
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2011 GERRY KOZIOL WWM REVIEW Denied NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER
NEED PCRWRD CAPACITY REVIEW
NEED WW/IWC REVIEW & APPROVAL OF GREASE INTERCEPTOR- TOM TOMCHAK 5025 W INA RD
NEED WW 5TH FLOOR CREDIT EVALUATION
04/21/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Door 100A and the future gate from the patio will need panic hardware. See IFC Chapter 10.
05/04/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; KEY NOTE 8.3: THE NOTE INDICATES A NEW 3'-0" DOOR, BUT THE PLAN INDICATES A DOUBLE DOOR. CLARIFY.
2. SHEET A4.2; NEW LINTEL DETAILS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. VERIFY.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/04/2011 ROBERT SHERRY WATER REVIEW Approved
05/05/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the termination of the T&P relief piping shown in detail 2/P3. Reference: Section 504.6, IPC 2006.
2. Verify the size of the gas pipe located between K14 and K31 (763 CFH at 70 feet) Reference: Section 402.3, IFGC 2006.
05/05/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the make up air duct within 18" of the Type I grease hoods complies with the requirements of Section 506.3.1.2, IMC 2006.
2. Revise the size of the grease ducts (EF-1, EF-2, and EF-4) to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.
3. Clarify the reason for installing bird screen and a backdraft damper for exhaust fans EF-1, EF-2, E-3, and EF-4 (note #4, fan schedule). Reference: Section 506.3.7, IMC 2006 and Section 904.11, IFC 2006.
4. Clarify the construction of the partition (Type 6D) located adjacent to the Type I hoods to ensure that it is built per Section 507.9, IMC 2006 with non-combustible supports (e.g. no plywood backing) and has a non-combustible, non-absorbent, cleanable surface (e.g. stainless steel) extending at least 18" beyond the hood.
05/13/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01131
7080 E 22ND ST #114
BrushFire BBQ

Electrical plans denied for the following:
1. Sheet E6, provide a location of the service.
2. Sheet E6, provide the size of the service entrance conductors.
3. Sheet E6, the new 4-500 mcm's (310 amps) feeding the new 600 amp CT feed a load of 539.3 amps ?
4. Panel K is only a single phase but has a 4 wire feeder going to it shown on Sheet E6.
5. Panels A, K, and KA all use the 65% demand factor as allowed per NEC for kit equipment, however the total load calculation using these factors equals 1199.3 amps on a
1200 amp service. This without the size of service entrance conductors noted. Since this service is being upgraded it should allow for future increases to it's ampacity.
5. How is the ampacity for the existing services obtained ?
6. Provide a front detail showing the demensions of the control enclosure to be supplied by Captive Air, concern is for the space it will require and how it will installed.



Ray T Majuta,
Elect Plan Ck,
PDSD, City of Tucson,
5/15/11
Ray.majuta@tucsonaz.gov
05/16/2011 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/01/2011 SUE REEVES OUT TO CUSTOMER Completed
06/01/2011 SUE REEVES REJECT SHELF Completed