| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/15/2011 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
| 06/16/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/22/2011 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 06/27/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/27/2011 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Item not resolved: comment number one from 05/09/11. Coordinate the proposed water heater support as shown in detail 8/S3.1 and in detail 1/P-401. Reference: Section 314.5 2006 UPC. 2. Provide a material schedule to include: DWV piping material, potable and non-potable water piping material. Type of piping insulation for hot and hot return piping, and pipe identification requirements. 3. Provide the method of sterilization to be used. Reference: Section 609.9 2006 UPC. 4. See detail 2/P-401; this activity is in the City of Tucson not in the Town of Surprise. |
| 06/30/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/30/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/07/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |