06/09/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01114
1501 S Eastside LP
Solar Pv System

1. Sheet 9, (interconnection pt #1) shows a connection to the line side of the 200 Amp Main CB, this type of connection is not allowed unless the equipment is listed for the application, free floating connections not approved, must be fixed terminals on the line side for PV conductor connection, TEP( Utility) will also deny.Please expand on this.
2. Sheet 9 (interconnection pt #2),you show 80 amp cb from PV supply and the Main CB for the service is a 150amp CB.
This equals 230 amps, the load center shown is 200 amps.
NEC 2005 ,690.64.B,the sum of the ampere ratings of overcurrent devices not to exceed the rating of the busbar
or conductors.



Ray Majuta
Elect Pln Ck,PDSD,
City of Tucson,
6/14/11