Permit Number - T11CM01112
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S2.1; FOUNDATION PLAN: PUT A REFERENCE ON THE PLAN FOR THE COLUMN AND FOOTING SIZES TO SHEET S2.0. 2. SHEET S3.0; DETAIL 103: NOTE 10 IS NOT INDICATED ON THE DETAIL. PROVIDE. 3. SHEET S4.0 (DETAIL 206); STRUCTURAL CALCULATIONS (SHEET 11): THE DETAIL INDICATES THE HORIZONTAL LEG OF THE ANGLE IS CONFIGURED DIFFERENTLY FROM THE CALCULATION. CLARIFY. IS THE SECTION AS SHOWN ON S4.0 ADEQUATE? 4. SHEET S4.0; DETAIL 202(X): IS THE DETAIL 9 REFERENCE ON THE PLAN SECTION CORRECT? VERIFY. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/17/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |