Permit Number: T11CM01112
Parcel: 116263500

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM01112
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S2.1; FOUNDATION PLAN: PUT A REFERENCE ON THE PLAN FOR THE COLUMN AND FOOTING SIZES TO SHEET S2.0.
2. SHEET S3.0; DETAIL 103: NOTE 10 IS NOT INDICATED ON THE DETAIL. PROVIDE.
3. SHEET S4.0 (DETAIL 206); STRUCTURAL CALCULATIONS (SHEET 11): THE DETAIL INDICATES THE HORIZONTAL LEG OF THE ANGLE IS CONFIGURED DIFFERENTLY FROM THE CALCULATION. CLARIFY. IS THE SECTION AS SHOWN ON S4.0 ADEQUATE?
4. SHEET S4.0; DETAIL 202(X): IS THE DETAIL 9 REFERENCE ON THE PLAN SECTION CORRECT? VERIFY.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/17/2011 DELMA ROBEY OUT TO CUSTOMER Completed