Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM01094
Parcel: 12710017D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01094
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2011 CPIERCE1 ZONING REVIEW Needs Review
06/28/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/28/2011 CPIERCE1 WWM REVIEW Needs Review
06/28/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed, Fourth request. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Comment not addressed, Fourth request. The branch piping sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
3. Comment not addressed, Fourth request. Provide calculations to support the scupper design or Revise the size of the provided scuppers to comply with the requirements of Section 1101.11.2.1, UPC 2006. Reference: Sections 1101.11.1 and 1101.11.2.1, UPC 2006.
4. Comment not addressed, Second request. Revise the meter and backflow preventer sizes shown on sheet P2.0 (Water Calculations) to match the verified sizes shown on sheet A1.0.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2011 CPIERCE1 OUT TO CUSTOMER Completed