Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM01094
Parcel: 12710017D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01094
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/24/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed, third request. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Comment not addressed, third request. The branch piping sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
3. Comment not addressed, third request. Provide calculations to support the scupper design or Revise the size of the provided scuppers to comply with the requirements of Section 1101.11.2.1, UPC 2006. Reference: Sections 1101.11.1 and 1101.11.2.1, UPC 2006.
4. Revise the meter and backflow preventer sizes shown on sheet P2.0 (Water Calculations) to match the verified sizes shown on sheet A1.0.
06/24/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed, third request. Provide energy code compliance calculations for the building envelope (the correct climate zone is Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
06/24/2011 ROBERT SHERRY WATER REVIEW Approved
06/28/2011 DROBEY1 ZONING REVIEW Needs Review
06/28/2011 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2011 DELMA ROBEY OUT TO CUSTOMER Completed