Permit Number: T11CM01068
Parcel: 13606013E

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM01068
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2011 DAVE MANN FIRE REVIEW Approved
04/28/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/03/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01068
2560 S Harrison Rd
19KW DC Photovoltalic Systrm


Electrical plans denied for ther following:

1. NEC 690.64.B.2, the sum of the ampere ratings of the overcurrent devices in circuits supplying power to a busbar shall not exceed the rating of the busbar.This would be at the new 125 amp panel.Keep in mind we are in the 2005 NEC.
2. Sheet PV 1.0, under notes #1, 690.1(A)(1), not found in NEC.
3. Explain the use of .5 to multiply and labeled under 690.7, when the figure should be 1.35 ? (Sheet PV 1.0.
4. Explain Max voltage 388.2v on sheet PV 1.0.

Please recheck calculations.

Ray Majuta,
Elect Pln CK,PDSD, City of Tuc,
5/5/11,
Ray.majuta@tucsonaz.gov