Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T11CM01068
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/12/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
04/28/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/03/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM01068 2560 S Harrison Rd 19KW DC Photovoltalic Systrm Electrical plans denied for ther following: 1. NEC 690.64.B.2, the sum of the ampere ratings of the overcurrent devices in circuits supplying power to a busbar shall not exceed the rating of the busbar.This would be at the new 125 amp panel.Keep in mind we are in the 2005 NEC. 2. Sheet PV 1.0, under notes #1, 690.1(A)(1), not found in NEC. 3. Explain the use of .5 to multiply and labeled under 690.7, when the figure should be 1.35 ? (Sheet PV 1.0. 4. Explain Max voltage 388.2v on sheet PV 1.0. Please recheck calculations. Ray Majuta, Elect Pln CK,PDSD, City of Tuc, 5/5/11, Ray.majuta@tucsonaz.gov |