Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM01066
Parcel: 125011230

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01066
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

New occupant load of first floor is great enough to require rated corridors. See IFC Section 1017.
04/14/2011 GERRY KOZIOL WWM REVIEW Approved
04/25/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide a new building occupant exiting floor plan analysis. Include first and second floor plan and new added office space. Comply with corridor fire ratings as per table 1017.1.
2. A new Certificate of Occupancy is required to be issued because of change in occupancy load. There can only be one address per certificate. Please have Pima County addressing department make all necessary address changes and correct the permit data accordingly.
3. Sheet AD111, Note 3, provide detail reference.
4. The new ramp has incorrect keynote reference.
5. Provide structural calculations for the following:
a. All new roof top mounted HVAC equipment
b. The new CMU wall opening steel lintel detail A1/A512.
END OF REVIEW
04/28/2011 ROBERT SHERRY WATER REVIEW Approved
04/28/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide tempered water supply from the water heater to the new shower and the existing lavatories per Section 607.1, IPC 2006.
2. Provide listing information for the specified shower drain. Reference: Section 303.4, IPC 2006.
3. Clarify the emergency drainage for the roof area served by the new 2" roof drain; no architectural details indicate the presence of any emergency drainage. Reference: Section 1107, IPC 2006.
4. Explain how primary and emergency drainage is accomplished for the west half of the roof. Reference: Section 106.3.1, IPC 2006.
5. Replot sheet PP121 so that the background is able to be scanned (see sheet A113 for a good example). Reference: Section 106.3.1, IPC 2006.
04/28/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Replot sheet MH121 so that the background is able to be scanned (see sheet A113 for a good example). Reference: Section 106.3.1, IMC 2006.
05/02/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2011 CPIERCE1 OUT TO CUSTOMER Completed
05/25/2011 SUE REEVES REJECT SHELF Completed