Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01066
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/12/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: New occupant load of first floor is great enough to require rated corridors. See IFC Section 1017. |
04/14/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
04/25/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide a new building occupant exiting floor plan analysis. Include first and second floor plan and new added office space. Comply with corridor fire ratings as per table 1017.1. 2. A new Certificate of Occupancy is required to be issued because of change in occupancy load. There can only be one address per certificate. Please have Pima County addressing department make all necessary address changes and correct the permit data accordingly. 3. Sheet AD111, Note 3, provide detail reference. 4. The new ramp has incorrect keynote reference. 5. Provide structural calculations for the following: a. All new roof top mounted HVAC equipment b. The new CMU wall opening steel lintel detail A1/A512. END OF REVIEW |
04/28/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/28/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide tempered water supply from the water heater to the new shower and the existing lavatories per Section 607.1, IPC 2006. 2. Provide listing information for the specified shower drain. Reference: Section 303.4, IPC 2006. 3. Clarify the emergency drainage for the roof area served by the new 2" roof drain; no architectural details indicate the presence of any emergency drainage. Reference: Section 1107, IPC 2006. 4. Explain how primary and emergency drainage is accomplished for the west half of the roof. Reference: Section 106.3.1, IPC 2006. 5. Replot sheet PP121 so that the background is able to be scanned (see sheet A113 for a good example). Reference: Section 106.3.1, IPC 2006. |
04/28/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Replot sheet MH121 so that the background is able to be scanned (see sheet A113 for a good example). Reference: Section 106.3.1, IMC 2006. |
05/02/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/25/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
05/25/2011 | SUE REEVES | REJECT SHELF | Completed |