Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01043
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2011 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 04/11/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/11/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/11/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/11/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: USE OF A SINGLE RESTROOM MUST BE APPEALED TO THE BUILDING OFFICIAL. SINCE THE OCCUPANCY LOAD IS OVER 15, AN APPEAL IS REQUIRED. 2. RESTROOM: PER IBC SECTION 1210.2, ANY SURFACE WITHIN 2' OF A FIXTURE MUST BE NON-ABSORBENT MATERIAL TO A HEIGHT OF 4'. PROVIDE. 3. SHEET A2.1; PARTITIONS: PROVIDE BRACING AT THE TOP OF NEW INTERIOR PARTITIONS AS REQUIRED BY IBC SECTION 1607.13. INCLUDE ON THE DRAWINGS A DETAIL INDICATING THE BRACING SIZE AND SPACING, AND THE CONNECTION OF THE BRACING TO THE TOP OF THE PARTITION WALL AND TO THE EXISTING STRUCTURE ABOVE. |
| 04/11/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/11/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a drinking fountain per Section 2902, IBC 2006. |
| 04/11/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/11/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 04/11/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/12/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |