Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
04/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the termination of the exhaust fan EF-1 is at least 10'-0" from the outside air intake from AC-1.
04/08/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01030
3867 N Oracle Rd

Electrical plans denied:

1. Circuits B-9,11 as spares in panel ?
2. Water Heater and Shutter motor both on B-5 ?
3. Mechanical Plans Examiner requires Exhaust fan to come on when air flows into room not connected to light.


Ray Majuta
Elec Pln CK,
PDSD, C of Tuc,
4/8/11,
04/08/2011 ROBERT SHERRY WATER REVIEW Approved
04/08/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS1: WITH 75 OCCUPANTS, THIS PROJECT REQUIRES 2 MALE AND 2 FEMALE WATER CLOSETS. REVISE.
2. SHEET A4.0 (DETAIL 2); STRUCTURAL CALCULATIONS (SHEET #2): CITY OF TUCSON AMENDMENTS TO THE IBC (1805.2) REQUIRE 18" DEPTH OF FOOTING TO GET 1500 PSF, OR 12" DEPTH FOR 1000 PSF. DETAIL 2 INDICATES 12" DEPTH, AND THE CALCS. INDICATE 1500 PSF. REVISE.
3. SHEET A4.0; DETAIL 3: A NOTE INDICATES 'STUDS PER ELEVATIONS'. WHERE ON THE ELEVATIONS ARE THEY LOCATED? VERIFY.
4. PROVIDE STRUCTURAL GENERAL NOTES.
04/08/2011 JASON GREEN ENGINEERING REVIEW Approved
04/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. All roof areas (e.g. the porch) shall be drained by roof drains, scuppers, or gutters. Reference: Section 1101.11.1, UPC 2006.
2. Provide listing information for the "c3100" Froet Industries roof drain - the company web site does not recognize that model number.
3. Provide structural calculations to show that the roof is capable of supporting the additional rain load due to the apparent height of the roof drain overflow. Reference: Sections 1101.11.1 and 1101.11.2.1, UPC 2006, and Section 1611.1, IBC 2006.
4. Revise the overflow drain to include a strainer. Reference: Section 1105.2, UPC 2006.
5. Show that the rainwater collector boxes are equipped with an overflow. Reference: Section 1101.11.2, UPC.
04/08/2011 MARTIN BROWN FIRE REVIEW Approved
04/08/2011 ERIC NEWCOMB ADA REVIEW Passed
04/08/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/13/2011 CAGUILA1 WWM REVIEW Needs Review