Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM00984
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/24/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/25/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved. Provide the dimensions or a reference to the appropriate details for the sizes of the scuppers and collector boxes. {Second Comment: Revise the roof plan (2/A9.10) to include either the dimensions or a reference to the appropriate details for the sizes of the scuppers, collector boxes, and downspouts for the ramada.} [Original comment: Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Sections 1101.2, 1101.7, 1106.4, and 1107, IPC 2006.] |
| 06/01/2011 | CAGUILA1 | WWM | REVIEW | Needs Review |