Permit Number: T11CM00984
Parcel: 117043440

Address:
550 N 5TH AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T11CM00984
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2011 DAVE MANN FIRE REVIEW Approved
05/04/2011 GERRY KOZIOL WWM REVIEW Denied NEEDS TO BUILD PUBLIC SEWER
NEED 3RD FL PCRWRD CAPACITY REVIEW- CHAD AMATEAU- 740-6547
05/09/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
05/10/2011 DAVID RIVERA ZONING REVIEW Approved
05/11/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the termination of the 6"-flue for the spa heater complies with the requirements of Section 503.5.4, IFGC 2006.
2. Provide specifications for the exhaust fan for the pool equipment room.
[Original Comment: Provide a mechanical plan for this building, including any exhaust fans or other mechanical equipment that will be installed. Reference: Section 106.3.1, IMC 2006.]
05/11/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the roof plan (2/A9.10) to include either the dimensions or a reference to the appropriate details for the sizes of the scuppers, collector boxes, and downspouts for the ramada. [Original comment: Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Sections 1101.2, 1101.7, 1106.4, and 1107, IPC 2006.]
05/11/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond The response to comment 5 indicates that the pool will be issued under a separate permit as a deferred submittal. If it is to have it's own separate permit it would not be considered a deferred submittal to this permit.
05/11/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
05/11/2011 RONALD BROWN ZONING HC REVIEW Passed
05/13/2011 LAITH ALSHAMI ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/24/2011 DELMA ROBEY OUT TO CUSTOMER Completed