Permit Number: T11CM00984
Parcel: 117043440

Address:
550 N 5TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00984
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a specification for the proposed shower and shower drain. Show how freeze protection will be provided. Reference: Sections 106.3.1 and 305.6, IPC 2006.
2. Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Sections 1101.2, 1101.7, 1106.4, and 1107, IPC 2006.
3. Provide a design for the natural gas utilization equipment proposed for the ramada, including combustion air, flues, and termination of the gas piping. Reference: Section 106.3.1, IFGC 2006.
04/04/2011 DAVE MANN FIRE REVIEW Denied SEE COMMENTS ON ACTIVITY T11CM00868
04/05/2011 DAVID RIVERA ZONING REVIEW Denied 1. Due to comments by review staff it appears that the development package site plan will have to be revised. Ensure that the Architectural site plan in the building package is revised to match the revised development plan.

2. While it appears that the building footprints match the unapproved version of the development plan foot prints the actual dimensions could not be verified. The building footprints on the development package are not dimensioned. Include a copy of the footprints from the development package or include it in the development package for review.

3. Ensure that the bicycle parking facilities are depicted on the first-floor plans sheets where applicable.

4. Zoning has reviewed the building plans for zoning requirements. While zoning finds the building plans in substantial compliance with the not-approved development package site the building plans cannot be approved at this time. All building plans must be approved by all commercial plans reviewers and approval of the development package is required. A copy of the approved and stamped development package must be included with the building plans on the next submittal. Also, there is an appeal to the MDR process pending and that must be addressed (prior to zoning approval).

5. Address zoning and all other comments prior to re-submittal of the building plans.
04/05/2011 GERRY KOZIOL WWM REVIEW Denied need to build public sewer
need 3rd floor pcrwrd capacity review- 740-6547- Chad Amateau
04/06/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied Provide cut sheets for equipment & motors
04/06/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/06/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON T11CM00868
04/06/2011 LAITH ALSHAMI ENGINEERING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
05/24/2011 DELMA ROBEY OUT TO CUSTOMER Completed
05/24/2011 DELMA ROBEY REJECT SHELF Completed