Permit Number: T11CM00977
Parcel: 116183320

Address:
450 N GRANDE AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T11CM00977
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/09/2011 ROBERT SHERRY WATER REVIEW Denied Comment not resolved. The revised site drawing shows the location of a 2" water meter but it appears to be located on an adjacent parcel. In addition, no reduced pressure backflow preventer assembly is shown. Reference: Section 103.2.3, UPC 2006.
06/09/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Show that the restroom floors slope toward the floor drains. Reference: Section 411.2, UPC 2006
2. Comment not resolved. The specified urinal uses only 1-gallon per flush but the flush valve is typically open for only 4-seconds which results in a flow rate of approximately 15 GPM. At 15 GPM, the water velocity in Type L copper is 9.9 feet per second. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
06/09/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2006 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2006. [Comment not addressed; Pima County records list this building as vacant, not an existing church. Provide calculations demonstrating adequate ventilation for the proposed occupancy of this building. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.]
06/10/2011 GBONILL1 ZONING REVIEW Needs Review