Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T11CM00977
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/04/2011 | STEVE SHIELDS | ZONING | REVIEW | Needs Review | |
04/04/2011 | JASON GREEN | ENGINEERING | REVIEW | Needs Review | |
04/05/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/05/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET TS.1; PROVIDE INFORMATION AS TO OCCUPANCY TYPE AND FIRE PREVENTION SYSTEMS. 2. SHEET A.1: PROVIDE DRINKING FOUNTAIN AND SERVICE SINK ON DRAWINGS. 3. SHEET A.1: PROVIDE DETAIL FOR BRACING TOP OF INTERIOR PARTITION WALLS, INCLUDING BRACING SIZE AND SPACING, AND BRACING CONNECTION TO TOP OF PARTITION WALL AND TO EXISTING STRUCTURE ABOVE. 4. SHEET TS.1: PROVIDE PLUMBING COUNT PER CHAPTER 29 OF THE 2006 IBC AND INCLUDE ON DRAWING. 5. SHEET A.1; ELEVATION 2: DISTANCE TO PAPER DISPENSER SHOULD BE 7"-9" TO CENTERLINE OF DISPENSER PER ICC/ANSI A117.1-2003, FIGURE 604.7. |
04/05/2011 | ENEWCOM1 | ADA | REVIEW | Passed | |
04/05/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Onsite fire turn-around does not meet Development Standard for inside radius at handicapped parking. |