Permit Number: T11CM00977
Parcel: 116183320

Address:
450 N GRANDE AV

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T11CM00977
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2011 STEVE SHIELDS ZONING REVIEW Needs Review
04/04/2011 JASON GREEN ENGINEERING REVIEW Needs Review
04/05/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/05/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS.1; PROVIDE INFORMATION AS TO OCCUPANCY TYPE AND FIRE PREVENTION SYSTEMS.
2. SHEET A.1: PROVIDE DRINKING FOUNTAIN AND SERVICE SINK ON DRAWINGS.
3. SHEET A.1: PROVIDE DETAIL FOR BRACING TOP OF INTERIOR PARTITION WALLS, INCLUDING BRACING SIZE AND SPACING, AND BRACING CONNECTION TO TOP OF PARTITION WALL AND TO EXISTING STRUCTURE ABOVE.
4. SHEET TS.1: PROVIDE PLUMBING COUNT PER CHAPTER 29 OF THE 2006 IBC AND INCLUDE ON DRAWING.
5. SHEET A.1; ELEVATION 2: DISTANCE TO PAPER DISPENSER SHOULD BE 7"-9" TO CENTERLINE OF DISPENSER PER ICC/ANSI A117.1-2003, FIGURE 604.7.
04/05/2011 ENEWCOM1 ADA REVIEW Passed
04/05/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Onsite fire turn-around does not meet Development Standard for inside radius at handicapped parking.