Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00957
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/12/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. For additional review fee assessment, please provide a letter to the building official, Mr. Ron Boose, outlining all the deferred submittals intended for this project. 2. Please provide special inspector certification for approval as outlined on the cover sheet and sheet S1.1. 3. Please delete all Applicable Code references not relative to this project. SHEET G1.0 4. Code Information is not legible. Please darken, reprint and resubmit. 5. Typical Accessibility Requirements is not the UBC, Chapter 31. Please delete these details in their entirety. a. All accessibility references are to be to the 2006 IBC, Chapter 11 and the ICC (ANSI 117./1, Edition 2003). b. Please do not use generic, code copied details. Please show all code compliance requirements, dimensions and accessories on the actual designed floor plans and elevations shown on sheets 4.0, A6.0 and A6.1. SHEET 4.0 6. At detail 3, several key note references and elevation references are incorrect. Please reconcile. 7. At detail 1, the new 3 form laminated partition for both toilet rooms has reduced the toilet stall width which does not allow for the required side clearance of 15" to the wall and/or partition from the center line of the toilet as required by the UPC, Section 406.7. a. Also, please confirm that the required distance from the wall for both accessible toilets is no less than 16" as per ICC (ANSI 117.1), Section 604.2. 8. Through out all the details of this sheet, several key note references and elevation references are incorrect. Please reconcile and resubmit. 9. Two new drinking fountains are shown. Please provide elevations of each showing one mounted for a wheelchair bound person and one for a standing person as required by Section 1109.5.1 and ANSI 602.4. END OF REVIEW |
| 04/14/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/19/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/20/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specification for WC-1 indicates "ADA compliance with riser assembly". Provide the manufacturer's literature that demonstrates compliance with the accessibility requirements of ANSI 117.1-2004. 2. Revise the specifications for water heater WH-2 to show the factory-set temperature limit required by Section 504.3, IECC 2006. 3. Key notes 6, 8, 10, and 11 on sheet M3.0 call for the installation of Watts Model 009 reduced pressure zone backflow preventers in cabinets or wall spaces. Show that each installation provides access per Section 603.3.4, UPC 2006 and the manufacturer's installation instructions. Provide an indirect waste receptor for each backflow preventer drain line per Sections 603.3.9 and 804.1, UPC 2006. (Note that the UPC does not require backflow protection for the water coolers (EWC-1) and that most coffee makers do not require reduced pressure zone backflow preventers since they do not create back-pressure.) 4. Verify that a vent will be provided for each fixture trap for the new floor drains. Reference: Sections 901.0 and 910.1, UPC 2006. 5. The specified drinking fountain for each building does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006. 6. One of the specified fixtures (Toto Neorest 600) requires a minimum water pressure greater than 15-PSI and a minimum flow rate of 8.7 GPM. Provide water pipe sizing calculations. Reference: Section 608.1, UPC 2006. |
| 04/20/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the balancing of the exhaust fans for the men's restroom in the showroom building to provide adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. |
| 04/26/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00957 3566 E Speedway TI Car Dealership Electrical plans denied for following: 1. Sheets E2.1 and E2.2 show quite a few circuits only identified by number, there are 3 panels in the area, please identify all circuits with panel name also. 2. Sheets E1.1 and E1.2 show a total of 192 fixtures, only 103 are listed in the IECC calculations ? 3. Provide a total load calculation. Ray T Majuta Elect Pln Ck, PDSD, City of Tucson, 4/25/11 Ray.majuta@tucsonaz.gov Elect |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/29/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 04/29/2011 | SUE REEVES | REJECT SHELF | Completed |